Selecting Cooling Architectures for High-Density AI Data Centres
Abstract
Rising power concentration in artificial intelligence servers has made cooling architecture a primary design constraint for high-density data centres. This paper compares recent peer-reviewed studies of air cooling, direct-to-chip cold plates, single- and two-phase immersion, and their environmental effects. The findings show that liquid cooling expands the thermal operating envelope of high-power hardware, although the size of the benefit depends on the measurement boundary. Direct-to-chip systems can retain a substantial air-side load, warmer coolant may increase server power, and immersion performance varies with flow distribution, fluid properties, and hardware design. Facility-level outcomes also depend on climate, electricity supply, water source, coolant production, and equipment lifetime. Cooling options should therefore be compared under a common workload and system boundary. Optimised air remains suitable for moderate-density or legacy facilities, direct-to-chip cooling provides a practical route for many high-density racks, and immersion is best suited to cases where exceptional heat density and purpose-built infrastructure justify changes to hardware and maintenance.
References
- Latif, I., Newkirk, A. C., Carbone, M. R., Munir, A., Lin, Y., Koomey, J., Yu, X., & Dong, Z. (2025). Single-node power demand during AI training: Measurements on an 8-GPU NVIDIA H100 system.IEEE Access, 13, 61740–61747. https://doi.org/10.1109/ACCESS.2025.3554728
- Xu, S., Zhang, H., & Wang, Z. (2023). Thermal management and energy consumption in air, liquid, and free cooling systems for data centers: A review.Energies, 16(3), 1279. https://doi.org/10.3390/en16031279
- Li, Y., Zhu, C., Li, X., & Yang, B. (2025). A review of non-uniform load distribution and solutions in data centers: Micro-scale liquid cooling and large-scale air cooling.Energies, 18(1), 149. https://doi.org/10.3390/en18010149
- Gupta, R., Asgari, S., Moazamigoodarzi, H., Pal, S., & Puri, I. K. (2020). Cooling architecture selection for air-cooled data centers by minimizing exergy destruction.Energy, 205, 117625. https://doi.org/10.1016/j.energy.2020.117625
- Ramakrishnan, B., et al. (2021). CPU overclocking: A performance assessment of air, cold plates, and two-phase immersion cooling.IEEE Transactions on Components, Packaging and Manufacturing Technology, 11(10), 1703–1715. https://doi.org/10.1109/TCPMT.2021.3106026
- Kang, D., Lee, J.-Y., Chakraborty, A., Lee, S.-E., Kim, G., & Yu, C. (2022). Recent advances in two-phase immersion cooling with surface modifications for thermal management.Energies, 15(3), art. 1214. https://doi.org/10.3390/en15031214
- Yuan, L., Wang, Y., Kosonen, R., Yang, Z., Zhang, Y., & Wang, X. (2024). Comparative study on heat dissipation performance of pure immersion and immersion jet liquid cooling system for single server.Buildings, 14(9), art. 2635. https://doi.org/10.3390/buildings14092635
- Muneeshwaran, M., Lin, Y.-C., & Wang, C.-C. (2023). Performance analysis of single-phase immersion cooling system of data center using FC-40 dielectric fluid.International Communications in Heat and Mass Transfer, 145, art. 106843. https://doi.org/10.1016/j.icheatmasstransfer.2023.106843
- Liu, C., & Yu, H. (2021). Evaluation and optimization of a two-phase liquid-immersion cooling system for data centers.Energies, 14(5), art. 1395. https://doi.org/10.3390/en14051395
- Hnayno, M., Chehade, A., Klaba, H., Bauduin, H., Polidori, G., & Maalouf, C. (2022). Performance analysis of new liquid cooling topology and its impact on data centres.Applied Thermal Engineering, 213, art. 118733. https://doi.org/10.1016/j.applthermaleng.2022.118733
- Stahlhut, M., Sekulla, M., Großöhme, P., Auweter, A., & Urbaneck, T. (2025). Data centers with direct liquid-cooled servers: Experimental analysis and modeling.Energy Science & Engineering, 13, 3605–3619. https://doi.org/10.1002/ese3.70116
- Haghshenas, K., Setz, B., Blosch, Y., & Aiello, M. (2023). Enough hot air: The role of immersion cooling.Energy Informatics, 6, art. 14. https://doi.org/10.1186/s42162-023-00269-0
- Siddik, M. A. B., Shehabi, A., & Marston, L. (2021). The environmental footprint of data centers in the United States.Environmental Research Letters, 16, art. 064017. https://doi.org/10.1088/1748-9326/abfba1
- Mytton, D. (2021). Data centre water consumption.npj Clean Water, 4, art. 11. https://doi.org/10.1038/s41545-021-00101-w
- Alissa, H. A., et al. (2025). Using life cycle assessment to drive innovation for sustainable cool clouds.Nature, 641, 331–337. https://doi.org/10.1038/s41586-025-08832-3