Simulation Study on Electric Field Characteristics of Buffer Layer Ablation Defects in High-Voltage Cables
Abstract
Due to insufficient broadband material parameters and frequency-dependent electric field data, the evolution mechanism of the buffer layer ablation defects in high-voltage cables under non-power-frequency excitation remains insufficiently understood. This paper addresses this gap by combining 20 Hz–10 MHz broadband dielectric testing with frequency-domain electric-field simulation to analyze the electromagnetic response characteristics of buffer-layer ablation defects across different developmental stages. Dielectric measurements reveal significant differences in relative permittivity and conductivity between dry and moistened water-blocking powders, demonstrating that moisture ingress markedly alters the partial electrical properties of the buffer layer. Simulation results indicate that the defect-region electric field exhibits pronounced frequency sensitivity rather than monotonic variation; notably, the field strength in the powder region may exceed the air breakdown threshold within the 100–200 Hz range—a critical phenomenon that conventional power-frequency analysis fails to capture. Furthermore, the most significant variation in field strength occurs within the 20–500 Hz band, suggesting a strong influence on partial discharge excitation. These findings demonstrate that relying solely on 50 Hz power-frequency results is insufficient to explain partial discharge initiation under non-power-frequency test voltages such as DAC and oscillating wave, underscoring the necessity of incorporating frequency-dependent material properties into discharge mechanism analysis, simulation modeling, and field diagnostic methodology.
References
- Wu, K., Zhao, G., Li, B., et al. (2026). High-voltage cable buffer layer ablation mechanism, research progress on detection technology and solutions.High Voltage Engineering, 52(2), 789-800.
- Chen, Y. (2019).High voltage XLPE fault characteristics and mechanism of cable buffer layer. South China University of Technology.
- Hui, B. (2023).High-voltage cable buffer layer ablation fault mechanism, research on defect detection and elimination methods. South China University of Technology.
- Liu, Y., & Chen, J. (2022). High voltage XLPE cable water-blocking buffer layer electrical–electro-thermal field analysis and simulated ablation test research.Proceedings of the CSEE, 42(4), 1260-1271.
- Liu, H., Liu, R., Zhao, X., et al. (2021). Study on buffer layer ablation of high-voltage XLPE cable induced by radial current concentration.Insulating Materials, 54(8), 94-101.
- Zheng, J., Su, X., Li, G., et al. (2022). Study on electrochemical corrosion characteristics and failure of high-voltage cable water-blocking buffer layer.Insulating Materials, 55(2), 91-96.
- Su, C. Q. (2010). Failure analysis of three 230kV XLPE cables. In2010 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America (T&D-LA)(pp. 22-25). IEEE.
- Zhao, X. (2021).Air gap discharge and electrochemical corrosion induced high-voltage XLPE research on cable buffer layer ablation fault mechanism[Doctoral dissertation, Xi'an Jiaotong University].
- Qiu, W., Zhang, Y., Xie, Y., et al. (2024). High voltage XLPE review of cable buffer layer defect research status.Insulating Materials, 57(4), 13-21.
- Zhang, K., Gao, J., Wu, K., et al. (2026). Mechanism study of insulation shield damage caused by high-voltage cable buffer layer ablation.Proceedings of the CSEE, 46(1), 445-454.
- Zhou, S., Liu, R., Jiang, L., et al. (2020). High voltage XLPE analysis of sheath ablation mechanism in insulated power cables.High Voltage Apparatus, 56(12), 171-176.
- Ouyang, B., Li, W., Liu, Y., et al. (2021). High voltage XLPE water-blocking buffer layer ablation mechanism.High Voltage Engineering, 47(9), 3153-3162.
- Duan, X., Liu, Y., Liu, S., et al. (2025). High voltage XLPE review of cable buffer layer ablation mechanism and detection methods.Transactions of China Electrotechnical Society, 40(5), 1541-1558.