Optimization of substation enclosure performance and carbon emission analysis based on OED
Abstract
To explore the thermal performance parameters of substation enclosure parameters and interaction and influence degree, using the DeST software simulation and orthogonal test method to building load minimum as the target parameters, select external wall heat transfer coefficient, roof heat transfer coefficient, outer window heat transfer coefficient and orthogonal test factors, carry out the four factors three level L9 (34) Orthogonal test analysis, studied the influence of each factor and its interaction on the building load, and finally obtained the optimal combination of factors under the comprehensive boundary conditions. At the same time, the correlation between load and outdoor temperature in the optimal scheme of unmanned substation and the carbon emission results before and after optimization are also explored. The results show that through univariate analysis, with the heat transfer coefficient of exterior wall, roof and window, the cumulative cooling load is not linear. Through the orthogonal experimental analysis, the significance of substation building is> roof exterior wall> south Angle> window, and the optimal is A1-B1-C2-D2The annual cumulative building cooling load is 20165.59 kW · h, and the peak cooling load appears on July 24. The operating condition of 0 ~ 9kW accounts for 90.6% of the annual operating time. There is a strong linear correlation between the building cooling load and the outdoor temperature (R2=0.65), the energy saving rate of the final optimized scheme is 17.71%, and the carbon saving rate is 26.72%. The research content of this paper provides reference for the renovation of existing buildings and the design of new buildings in substation buildings.
References
- The Xinhua News Agency. Speech by President Xi Jinping at the General Debate of the 75th Session of the United Nations General Assembly [EB / OL] .(2020-09-22) [2023-07-13] .https://www.gov.cn/xinwen/2020-09/22/content_5546169.htm.
- Zhang Jun. Research on energy saving technology of prefabricated cabin industrial buildings [D] . South China University of Technology, 2019.
- Xiong Tianjun, Li Guopeng, Liu Ye, etc. Research on the realization ways of near zero energy substation [J] . Building Energy Conservation (Chinese and English), 2021,49 (12): 39-44.
- Chen Weiying, Li Yixiang, Cao Di, etc. Research on indoor lighting optimization strategy of long-span old industrial buildings [J] . Industrial Buildings, 2022,52 (10): 139-145.
- Yi Er Yi, Yang Changzhi. Optimization combination of external envelope structure of office buildings in hot summer and cold winter areas [J] . Science, Technology and Engineering, 2022,22 (22): 9736-9745.
- Li H X, Li Y, Jiang B, et al.Energy performance optimisation of building envelope retrofit through integrated orthogonal arrays with data envelopment analysis [J] .Renewable Energy, 2020, 149: 1414-1423.
- Liu Z A, Hou J, Zhang L, et al.Research on energy-saving factors adaptability of exterior envelopes of university teaching-office buildings under different climates (China) based on orthogonal design and EnergyPlus [J] .Heliyon, 2022, 8(8): e10056.
- Qu Y, Zhou D, Xue F, et al.Multi-factor analysis on thermal comfort and energy saving potential for PCM-integrated buildings in summer [J] .Energy and Buildings, 2021, 241: 110966.
- Liu Qingyu, Guan Qi, Zhang Min, etc. Optimization design of solar energy assisted heating for typical rural houses in northern China [J] . Renewable Energy, 2020,38 (04): 447-452.
- Lu Jie, Wang Long, Sun Chengcai. Factors influencing air conditioning load in hospitals in cold areas [J] . Journal of Shenyang University of Technology, 2021,43 (05): 584-589.
- Shao Teng, Zheng Wuxing. Energy-saving sensitivity analysis of rural residential space design factors based on envelope performance difference [J] . Building Science, 2021,37 (04): 101-110 + 125.
- Lou Xiaog, Wang Xin, Si Pengfei, etc. Study on the influencing factors of multi-stage water tank variable capacity storage heat system for solar heating [J] . Building Science, 2023,39 (02): 97-104.
- Yang Changzhi, Chen Wang Xiaochen. Combination optimization method of delayed attenuation characteristics of building exterior walls [J] . Journal of Hunan University (Natural Science Edition), 2023,50 (05): 231-240.